How To Set Date On Honeywell Rth7500 Thermostat
RTH7400/RTH7500 RET97D Series
Possessor's Manual
This is a legacy product certificate supported by Resideo. It is no longer manufactured
Programmable Thermostat
Read and salvage these instructions.
For help please visit yourhome.honeywell.com
Installation is Easy
- Characterization wires and remove your old thermostat
- Install and wire your new thermostat
- Prepare your new thermostat to match your heating/cooling system
- This thermostat works with nigh all System Types
- Information technology is preset for the virtually common organisation
Do yous need assistance? We are here to help.
Call 1-800-468-1502 for wiring assistance earlier returning the thermostat to the store.
NO MERCURY NE PAS JETER LE MERCURE
ATTENTION: MERCURY RECYCLING NOTICE
This production does not incorporate mercury. However, this product may supercede a product that contains mercury. Mercury and products containing mercury should not be discarded in household trash. For more information on how and where to properly recycle a thermostat containing mercury in the United States, please refer to the Thermostat Recycling Corporation at www.thermostat-recycle.org. For mercury thermostat recycling in Canada, please refer to Switch the Stat at world wide web.switchthestat.ca
This thermostat contains a Lithium bombardment which may contain Perchlorate material. Perchlorate Material–special handling may apply, Run into www.dtsc.ca.gov/hazardouswaste/perchlorate
NOTICE: To avoid possible compressor damage, do not run air conditioner if the outside temperature drops beneath 50°F (ten°C).
Customer assistance
For aid with this production, please visit http://yourhome.honeywell.com.
Or phone call Honeywell Client Care toll-complimentary at 1-800-468-1502.
To save time, please note your model number and appointment code before calling.
Pull at bottom to remove thermostat from wallplate. Turn thermostat over to find model number and date code.
® U.S. Registered Trademark. Patents pending.
US Patent No. half-dozen,595,430; 7,114,554; vii,274,972; seven,225,054 and other patents awaiting
- Turn Off Power to Heating/Cooling Organisation
- Remove One-time Thermostat
Remove one-time thermostat but leave wallplate with wires fastened.
If you lot have an older thermostat with a sealed mercury tube, turn to page 2 for proper disposal instructions.
- Label Wires with Tags
Label the wires using the supplied wire labels as yous disconnect them.
- Carve up Wallplate from New Thermostat
Remove wallplate from the new thermostat and mount onto wall.
- Mountain Wallplate
Mount the new wallplate using the included screws and anchors.
Drill three/xvi-in. holes for drywall
Drill 3/32-in. holes for plaster - Connect Wires
Simply match wire labels.
If labels practice non match letters on the thermostat, check "Alternate Wiring (Conventional Systems)" on folio 6 and connect to terminal as shown here (see notes, below).
Nosotros are here to help. Call 1-800-468-1502 for wiring aid.
Alternate Wiring (Conventional Systems)
If labels do not lucifer terminals, connect wires equally shown here (see notes, below).
ane.Remove metal jumper connecting R and Rc just if you must connect both R and Rc wires.
2.If your old thermostat had both R and RH wires, remove metallic jumper. Connect the R wire to the Rc terminal, and the RH wire to the R terminal.
three.If your old thermostat had only 1 C or C1 wire, connect information technology to the C final. If your old thermostat had 2 C or C1 wires, wrap each separately with electric record and practice non connect them.
Alternating Wiring (Estrus Pump)
If labels do not friction match letters on thermostat, encounter folio 7.
NOTE: If East and Aux exercise not each have a wire connected, employ a modest slice of wire to connect them to each other.
Alternating Wiring (For Heat Pumps Only)
1.Exit metallic jumper in place, connecting R & Rc terminals.
2.If your old thermostat had both V and VR wires, stop now and contact a qualified contractor for assistance.
3.If your quondam thermostat had carve up O and B wires, attach the B wire to the C terminal.
4.If another wire is fastened to the C final, cease now and contact a qualified contractor for assistance.
5.If your erstwhile thermostat had Y1, W1 and W2 wires, terminate now and contact a qualified contractor for help.
half dozen.If 50 final is used, C concluding wire must be connected (contact a 5 contractor if at that place is no C wire).
6.If E and Aux terminals do not each have a wire connected, use a small 6 slice of wire to connect them to each other. - Install Batteries
Install ii AA alkaline batteries and remove tab.
- Install Thermostat onto Wallplate
Install thermostat onto the wallplate on the wall.
- Plow Ability Back On
Turn the power back on to the heating/cooling arrangement.
- Ready Time and Date
i. Printing
to set month, and then press NEXT.
2. Press
to set day, then press NEXT.
3. Press
to ready year, then press Washed.
4. Press
to set fourth dimension, then press DONE to save and go out.
- If your system blazon is…
If your organization blazon is:
Single Phase Heat and Cool
Congratulations, you're done!
If your system type is:
Multistage Heat and Absurd
Estrus Pump* without Fill-in Rut
Heat Pump* with Backup Heat
Heat But
Absurd Only
Continue with Advanced Installation on next page to match your thermostat to your organisation type.
*Oestrus Pump–an air conditioner that provides cooling in the summer, and also runs in reverse in the winter to provide heating.
If you are not certain of your system type or if you have other questions, telephone call us toll-free at i-800-468-1502.
This thermostat works on 24 volt or 750 mV systems. It will NOT work on 120/240 volt systems.
Advanced Installation
Enter System Setup
- Press and release the left push.
- Press and hold the center button until the screen changes (approximately five seconds).
Changing Settings
- Press the s or t button to change the setting.
- Printing NEXT to advance to next function.
- Printing DONE to save & leave.
NOTE: Some functions in the following pages may not appear due to previous selections fabricated.Office Description Setting
Press the
button to modify the setting. 0120 Year Setting (first two digits) 20 = Year xx twenty
21 = Yr 21 twenty0130 Year Setting (second ii digits) 01 – 99 (i.e., 2001 – 2099 0140 Month Setting 01 – 12 (i.eastward., January – Dec) 0150 Appointment Setting 01 – 31 Function Descriptions Setting
Printing the
button to alter the setting. 0170 Select Organization Type 1 Heat/cool: Gas, oil or electric heating with primal air conditioning.
2 Heat pump: Heat pump without backup or auxiliary heat.
3 Heat merely: Gas, oil or electric heat without central air conditioning.
four Estrus only with fan: Gas, oil or electric oestrus without central air workout.
5 Hot water oestrus but (no fan): Gas, oil or hot water heat without fundamental air-conditioning.
vi Cool only: Primal ac only.
7 Heat pump: Heat pump with backup or auxiliary heating.
viii Heat/Cool Multiple stages: 2 estrus stages (wires on W and W2), 2 cooling stages (wires on Y and Y2).
ix Heat/Cool Multiple stages: two heat stages (wires on W and W2), one cooling stage (wire on Y).
10Heat/Cool Multiple stages: ane heat stage (wire on West), 2 cooling stages (wires on Y and Y2).0180 Heating Fan Control 0 Gas or oil rut: Utilize this setting if y'all accept a gas or oil heating system (system controls fan operation).
i Electric heat: Utilize this setting if you take an electric heating system (thermostat controls fan operation).0190 Heat Pump Changeover Valve (for oestrus pumps only) 0 Cooling changeover valve: Use this setting if you connected a wire labeled "0" to the 0/B last (run across page 6).
i Heating changeover valve: Use this setting if you lot connected a wire labeled "B" to the 0/B last (encounter folio seven).0240 Heating Cycle Rate 5 Gas or oil furnace: Standard gas/oil furnace (less than xc% efficiency).
9 Electrical furnace: Electrical heating systems.
3 Estrus pump, hot water or loftier-efficiency furnace: Hot h2o
system or gas furnace (more than ninety% efficiency).
1 Gas/oil steam or gravity organization: Steam or gravity oestrus systems.0270 Emergency Heat Cycle Rate (rut pumps only) ix Electric furnace: Electric heating systems. 0300 Manual/Auto Changeover 0 Manual changeover (Estrus/CooV0f1).
ane Automated changeover (Heat/CooVAuto/Off). Automatically turns on Heat or Cool based on room temperature. Note: Arrangement maintains minimum iii°F difference between oestrus and cool settings.0320 Temperature Format (°F/°C) 0 Fahrenheit ane Celsius 0330 Daylight Saving Fourth dimension On/Off 0 Off: No adjustment for daylight saving time.
1 On: Auto-change to daylight saving fourth dimension (for areas that exercise not use the new 2007 DST calendar).
2 On: Auto-modify to daylight saving time (2007 and beyond, for areas that use the new 2007 DST calendar).0500 Furnace Filter Change Reminder 0 Off (no reminder)
1 Reminder in about 1 month
two Reminder in about 3 months
3 Reminder in about 6 months
4 Reminder in about 9 months
five Reminder in virtually one year
6 Reminder in virtually 3 years0530 Smart Response® Technology i On 0 Off 0600 Maximum Estrus Setting xc°F (other options: 40-89°F [4-32°C]) 0610 Minimum Cool Setting l°F (other options: 51-99°F [11-37°C]) 0640 Clock Format 1212-hour clock (i.e., "iii:30 pm") 2424-hour clock (i.due east., "15:xxx")
Nearly your new thermostat
Your new Honeywell thermostat has been designed to give you lot many years of reliable service and easy-to-use, button-button climate command.
- Easy-to-follow menu programming.
- One-touch on temp command overrides program schedule at any time.
- Precise comfort control keeps temperature within i°F of the level you fix.
- Change/check reminder lets you know when to supersede furnace filter.
- Large display with backlight is easy to read–fifty-fifty in the dark
Thermostat controls
Display screen
…Arrangement to select:
Heat: Heating organisation control.
Cool: Cooling system command.
Machine: Thermostat automatically selects heating or cooling depending on the indoor temperature.
Off: All systems off. Em
Heat: Emergency & Auxiliary Heat control. Compressor is locked out. (Select models merely.)
…FAN to select:
Car: Fan runs only when heating or cooling arrangement is on.
On: Fan runs continuously.
Press DONE to go out and salve settings.
Clock setting
- To set the electric current time display, press CLOCK & More than, then press
or
to conform the time. Press and agree
or
to advance the time more quickly. - Printing DONE to salve & leave (or press Go BACK to go out without irresolute the time).
NOTE: The existent-time clock should never require aligning since it automatically updates for daylight savings time, and stores all date/time information.
Program Schedule
You can program four time periods each solar day, with unlike settings for weekdays and weekends. Nosotros recommend the pre-set up settings (shown in the tabular array below), since they can reduce your heating/cooling expenses.
Wake – Set to the time you awaken and the temperature you want during the morning, until you get out for the day.
Leave – Set to the fourth dimension you leave domicile and the temperature you lot want while you are away (usually an energy-saving level).
Return – Set to the fourth dimension you return abode and the temperature you desire during the evening, until bedtime.
Slumber – Fix to the time y'all go to bed and the temperature you want overnight (usually an energy-saving level).
NOTE: Leave and Render periods can be canceled on weekends.
To suit plan schedules (RTH7400 only)
- Press SCHEDULE, and then EDIT to see weekdays.
- Press SELECT DAY to highlight Mon-Fri (they will share the same settings).
- Press Next Step twice, and so printing
to set Wake fourth dimension for selected days. - Press NEXT STEP, then
to set Rut temperature for this time menses. - Press NEXT STEP, and so
to set Cool temperature for this fourth dimension period. - Repeat steps three-5 to plan other time periods (LEAVE, Return, SLEEP), then press Washed.
- Repeat steps one-6 to program Sabbatum/ Sunday. (Press
until the desired day is flashing, and then press SELECT DAY.) - Printing DONE to save & leave.
To adapt program schedules (RTH7500/RET97D only)
- Press SCHEDULE, then EDIT to encounter weekdays.
- Press SELECT DAY. You can select multiple days to program with the same settings.
- Press NEXT STEP twice, then printing
to set Wake time for selected day(s). - Press NEXT Footstep, then
to set Heat temperature for this time period. - Printing Adjacent Pace, then
to gear up Cool temperature for this time period. - Repeat steps 3-5 to plan other time periods (Go out, RETURN, Slumber), and then press Done.
- Echo steps one-half-dozen to programme any remaining days. (Press
until the desired twenty-four hour period is flashing, and then printing SELECT DAY.) - Press Washed to relieve & exit.
Program schedule override (temporary)
Press
to immediately adjust the temperature. This will temporarily override the temperature setting for the current time menses. The new temperature will be maintained until the next fourth dimension period. When the timer expires, the program schedule volition resume and set the temperature to the level y'all've programmed for the electric current time period. To cancel the temporary setting at any time, press USE SCHEDULE.
Plan schedule override (permanent)
Press
to arrange temperature, and then press HOLD. This will turn off the program schedule. Whatever temperature you set will exist maintained 24 hours a mean solar day, until yous manually change it, or press Utilize SCHEDULE to cancel "Hold" and resume the plan schedule.
Automobile changeover
Use this feature in climates where both air-conditioning and heating are used on the same twenty-four hour period. When the system mode is in Auto, the thermostat automatically selects heating or cooling depending on the indoor temperature.
While in the Motorcar mode, if a schedule override takes place (temporarily or permanently) the thermostat will automatically accommodate the cooling and heating settings to maintain a 3-degree separation between the cool and oestrus settings.
For instance, if the heat temperature is raised to where it gets within iii-degrees of the cool setting, the brandish will testify an up arrow adjacent to "Absurd" to show the thermostat is raising the cool setting up to maintain a 3-degree separation. The brandish volition as well show both "Auto" and either "Heat" or "Cool" for which temperature setting yous are currently adjusting. Printing the organisation button to select between the heat and absurd to view/adjust either mode.
Circumspection: To avoid possible compressor damage, do not use Auto Changeover if the outside temperature drops beneath l°F (10°C).
Filter reminder
If activated during installation, the furnace filter reminder alerts you when it is time to replace your filter. Press RESET after changing the filter, to restart the timer. To reset the reminder interval earlier it expires:
- Press More, then Next.
- Press RESET.
- Press DONE to save and get out.
Special features
Smart Response® Engineering science: This feature allows the thermostat to "larn" how long the furnace and air conditioner take to reach programmed temperature settings, so the temperature is reached at the time you set. For instance: Gear up the Wake fourth dimension to 6 am, and the temperature to 70°. The oestrus volition come up on before half-dozen am, so the temperature is 70° by the fourth dimension you wake at 6. The message "Recovery" is displayed when the system is activated before a scheduled time period.
Compressor Protection: This characteristic forces the compressor to wait a few minutes before restarting, to prevent equipment impairment. During the wait fourth dimension, the bulletin "Wait" is displayed on screen.
Machine Changeover: This feature is used in climates where both ac and heating are used on the same mean solar day. When the system is set to Automobile, the thermostat automatically selects heating or cooling depending on the indoor temperature. Heat and cool settings must be at least 3 degrees autonomously. The thermostat will automatically adjust settings to maintain this 3-caste separation.
Battery replacement
Batteries are optional (to provide backup power) if your thermostat was wired to run on AC power when installed. Install fresh batteries immediately when the LO BATT warning begins flashing. The alert flashes almost 30 days earlier batteries are depleted. Even if the alarm does not announced, you should supercede batteries one time a twelvemonth, or earlier leaving dwelling house for more than than a calendar month.
Grasp thermostat and pull to remove from wallplate
Troubleshooting
If you lot have difficulty with your thermostat, please try the post-obit suggestions. Most problems can be corrected rapidly and easily.
| Display is blank | • Check circuit billow and reset if necessary. • Brand sure power switch at heating & cooling arrangement is on. • Make sure furnace door is closed securely. • Make certain fresh AA alkaline batteries are correctly installed. |
| Temperature settings practise not change | Brand sure heating and cooling temperatures are set to acceptable ranges: • Rut: twoscore° to 90 °F (4.v° to 32 °C). • Cool: 50° to 99 °F (x° to 37 °C). |
| Heating or cooling system does non answer | • Press System to ready system to Estrus. Brand sure the temperature is set higher than the Inside temperature. • Press SYSTEM to set arrangement to Absurd. Make sure the temperature is set lower than the Inside temperature. • Bank check excursion breaker and reset if necessary. • Brand sure power switch at heating & cooling system is on. • Make sure furnace door is airtight securely. • Wait 5 minutes for the system to respond. |
| Cannot change system setting to Cool | • Check Function 0170: System Type to make sure it is fix to match your heating and cooling equipment. |
| Fan does not turn on when heat is required | • Check Office 0180: Heating Fan Control to make sure it is set to friction match your heating equipment. |
| Heating system is running in cool mode | • Check Role 0170: System Blazon to make sure it is gear up to friction match your heating and cooling equipment. |
| Scarlet light is on | • If thermostat is in Emergency Estrus mode the red light is normal. It shows that the thermostat is in emergency heat manner. • If thermostat is not in Emergency Estrus manner, contact a qualified service contractor for repair. |
| "Wait" appears on the screen | • Compressor protection feature is engaged. Expect 5 minutes for the system to restart safely, without damage to the compressor. |
| Estrus pump issues cool air in rut mode, or warm air in absurd mode | • Check Part 0190: Oestrus Pump Changeover Valve to make sure it is properly configured for your system. |
For help with this product, delight visit http://yourhome.honeywell.com or phone call Honeywell Customer Intendance toll-free at one-800-468-1502.
one-year limited warranty
Honeywell warrants this product, excluding battery, to be free from defects in the workmanship or materials, under normal use and service, for a menses of one (i) year from the date of buy past the consumer. If at any time during the warranty period the product is determined to exist defective or malfunctions, Honeywell shall repair or supercede it (at Honeywell's selection).
If the product is lacking,
(i) return it, with a bill of sale or other dated proof of purchase, to the place from which yous purchased information technology; or
(2) phone call Honeywell Client Care at ane-800-468-1502. Client Care will brand the determination whether the product should exist returned to the following address: Honeywell Return Goods, Dock 4 MN10-3860, 1885 Douglas Dr. N., Aureate Valley, MN 55422, or whether a replacement product tin be sent to yous.
This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Honeywell that the defect or malfunction was acquired past damage which occurred while the product was in the possession of a consumer.
Honeywell's sole responsibility shall be to repair or supervene upon the production within the terms stated in a higher place. HONEYWELL SHALL Non Exist LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING Whatsoever INCIDENTAL OR CONSEQUENTIAL Damages RESULTING, DIRECTLY OR INDIRECTLY, FROM Whatsoever Alienation OF ANY WARRANTY, Limited OR IMPLIED, OR ANY OTHER FAILURE OF THIS Production. Some states practise not allow the exclusion or limitation of incidental or consequential damages, and then this limitation may non apply to you.
THIS WARRANTY IS THE ONLY Limited WARRANTY HONEYWELL MAKES ON THIS Product. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A Particular PURPOSE, IS HEREBY Express TO THE ONE-Twelvemonth Duration OF THIS WARRANTY.
Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. This warranty gives you specific legal rights, and you may accept other rights which vary from state to state.
If you have any questions apropos this warranty, please write Honeywell Customer Relations, 1985 Douglas Dr, Gold Valley, MN 55422 or call i-800-468-1502.
Automation and Command Solutions
Honeywell International Inc.
1985 Douglas Drive North
Gilded Valley, MN 55422
yourhome.honeywell.com
® U.Southward. Registered Trademark.
© 2022 Honeywell International Inc.
33-00090EF–01 1000.South. 07-xv
Printed in United statesA.
Documents / Resources
How To Set Date On Honeywell Rth7500 Thermostat,
Source: https://manuals.plus/honeywell/rth7400rth7500-ret97d-series-programmable-thermostat-manual
Posted by: gehlnotionned.blogspot.com